Tel:
+86 (21) 6897 9561
Fax:
+86 (21) 6897 9562
Email:
info@asiaron.com
| |
Electric porcelain
>>> High Voltage Pin Insulator
High
Voltage Pin Insulator
Technical data
|
Enterprise standard
- A1001
- A1002
- A1003
- A1004
- A1005
- A1006
- A1007
|
 |
|
Code |
A1001 |
A1002 |
A1003 |
A1004 |
|
Figure |
1 |
1 |
2 |
3 |
|
Grade |
P-11-Y |
P-15-Y |
P-120-Y |
P-33-Y |
|
Main dimension (mm) |
H |
133 |
137 |
195 |
244 |
|
h |
48 |
48 |
52.63 |
52.63 |
|
D |
140 |
152 |
230 |
279 |
|
d |
18.29 |
18.29 |
27.78 |
27.78 |
|
R1 |
13 |
13 |
19 |
19 |
|
R2 |
9.5 |
12.7 |
14.3 |
13 |
|
Normal voltage (kv) |
11 |
15 |
22 |
33 |
|
Creepage distance (mm) |
240 |
298 |
432 |
630 |
|
Minimum flashover voltage (kv) |
power frequency voltage |
Dry |
75 |
80 |
100 |
135 |
|
Wet |
45 |
55 |
60 |
65 |
|
50% Impulse voltage |
Positive pole |
100 |
130 |
160 |
185 |
|
Negative pole |
110 |
175 |
205 |
|
|
Withstand voltage (kv) |
1 minute power frequency voltage |
Dry |
65 |
70 |
90 |
110 |
|
Wet |
40 |
50 |
55 |
75 |
|
Impulse voltage |
|
110 |
150 |
|
|
Radio interference voltage (RIV) (kv) |
voltage testing to ground |
15 |
15 |
22 |
30 |
|
Max RIV at 1000kHz/uV |
8000 |
8000 |
12000 |
16000 |
|
Power frequency puncture voltage (kv) |
135 |
135 |
145 |
185 |
|
Tensile strength (kn) |
11 |
11 |
11 |
13 |
|
Weight (kg) |
1.8 |
|
|
11.5 |
|
Code |
A1005 |
A1006 |
A1007 |
|
Figure |
1 |
2 |
3 |
|
Grade |
Pw-11-Y |
Pw-22-Y |
Pw-33-Y |
|
Main dimension (mm) |
H |
185 |
255 |
320 |
|
h |
52.63 |
52.63 |
52.63 |
|
D |
170 |
205 |
240 |
|
d |
76 |
76 |
76 |
|
d1 |
27.78 |
27.78 |
27.78 |
|
R1 |
16 |
16 |
16 |
|
R2 |
16 |
16 |
16 |
|
Normal voltage (kv) |
15 |
22 |
33 |
|
Creepage distance (mm) |
432 |
673 |
851 |
|
Minimum flashover voltage (kv) |
power frequency voltage |
Dry |
100 |
125 |
140 |
|
Wet |
65 |
95 |
110 |
|
50% Impulse voltage |
Positive pole |
150 |
190 |
210 |
|
Negative pole |
|
|
|
|
Withstand voltage (kv) |
1 minute power frequency voltage |
Dry |
90 |
110 |
125 |
|
Wet |
60 |
90 |
100 |
|
Impulse voltage |
140 |
180 |
200 |
|
Radio interference voltage (RIV) (kv) |
voltage testing to ground |
22 |
30 |
44 |
|
Max RIV at 1000kHz/uV |
12000 |
16000 |
25000 |
|
Power frequency puncture voltage (kv) |
135 |
135 |
145 |
|
Tensile strength (kn) |
11 |
11 |
11 |
|
Weight (kg) |
5 |
10 |
13 |
Australilia
standard (AS) |
- 10141
- 10142
- 10143
- 10144
- 10145
- 10146
- 10147
- 10148
- 10149
|
 |
|
Code |
10141 |
10142 |
10143 |
10144 |
10145 |
10146 |
10147 |
10148 |
10149 |
|
AS Type |
LP.LV |
SLP11/180 |
ALP11/275 |
ALP22/450 |
|
ALP22/480 |
|
ALP22/520 |
ALP22/920 |
|
Figure |
1 |
2 |
5 |
4 |
4 |
3 |
3 |
6 |
7 |
|
Minimum nominal creepage distance (mm) |
|
180 |
275 |
450 |
490 |
480 |
510 |
520 |
920 |
|
Main dimension (mm) |
H |
91 |
110 |
200 |
200 |
240 |
200 |
196 |
215 |
320 |
|
h |
32.5 |
40 |
66.5 |
66.5 |
66.5 |
66.5 |
66.5 |
66.5 |
66.5 |
|
D |
82 |
150 |
160 |
160 |
165 |
260 |
280 |
205 |
240 |
|
d |
48 |
76 |
76 |
76 |
76 |
80 |
113 |
78 |
76 |
|
R1 |
11 |
16 |
16 |
16 |
16 |
16 |
16 |
16 |
16 |
|
R2 |
11 |
13 |
13 |
16 |
16 |
16 |
13 |
16 |
16 |
|
Tensile strength (kn) |
7 |
7 |
7 |
11 |
11 |
11 |
11 |
11 |
11 |
|
Power frequency wet withstand voltage (kv) |
|
30 |
30 |
50 |
50 |
50 |
68 |
50 |
90 |
|
Lightning impulse withstand voltage (kv) |
|
105 |
105 |
150 |
160 |
150 |
180 |
150 |
220 |
|
Power frequency puncture voltage (kv) |
|
95 |
95 |
130 |
160 |
169 |
170 |
145 |
185 |
|
Weight (kg) |
0.6 |
1.5 |
3 |
3.5 |
4.4 |
6.8 |
6.3 |
7.3 |
13.4 |
American
standard (ANSI) |
- 10121
- 10122
- 10123
- 10124
- 10125
|
 |
|
Code |
10121 |
10122 |
10123 |
10124 |
10125 |
|
American standard (ANSI) |
Jan-55 |
Feb-55 |
Mar-55 |
Apr-55 |
May-55 |
|
Figure |
16 |
17 |
18 |
18 |
18 |
|
Dimension (mm) |
D |
83 |
95 |
121 |
140 |
178 |
|
H |
89 |
83 |
95 |
111 |
124 |
|
h |
44 |
38 |
38 |
44 |
51 |
|
Creepage distance (mm) |
102 |
127 |
178 |
229 |
305 |
|
Minimum pin Length (mm) |
102 |
102 |
127 |
127 |
152 |
|
Tensile Strength (Kn) |
3000 (13) |
2500 (11) |
2500 (11) |
3000 (13) |
3000 (13) |
|
Power frequency flashover voltage (kv) |
Dry |
35 |
50/45 |
65/55 |
70/65 |
85/80 |
|
Wet |
20 |
25 |
35/30 |
40/35 |
45 |
|
Impulse flashover voltage (kv) |
Positive pole |
50 |
75/70 |
100/90 |
110/105 |
140/130 |
|
Negative pole |
70 |
95/85 |
130/110 |
140/130 |
170/150 |
|
Power frequency puncture voltage (kv) |
50 |
70 |
90 |
95 |
115 |
|
Radio interference voltage (RIV) (kv) |
voltage testing to ground |
5 |
5 |
10 |
10 |
15 |
|
Max RIV at 1000kHz/uV |
2500/50 |
2500/50 |
5500/50 |
5500/50 |
8000/50 |
|